Fault phenomenon and cause of gas burner
Jul 15, 2023
Fault phenomenon and cause of industrial gas burners
Fault phenomenon of the industrial gas burner: When the power is turned on, the burner does not start, and the control box does not light up the fault light. the
Possible Causes:
(a) It might just be a minor problem, like the power not turning on. It may also be that the gas switch ball valve has not been opened or the gas pressure is insufficient (lower than the set value on the gas low pressure switch). (b) Please check the fuse of the power supply, and check whether the temperature adjusted on the thermostat is appropriate. If the burner is connected to other automatic control devices at the same time, please check whether there is no power supply to the burner due to the influence of these devices. the
(c) Please check whether the voltage is normal. The control box of the industrial burner basically has a low voltage protection function. When the voltage is too low, the burner cannot start. the
(d) Please check whether the control box of the industrial burner is firmly plugged into the socket, and also check whether the power wiring is loose or falling off. the
(e) The control box may be malfunctioning (damaged).