Debugging of industrial boiler burners
Oct 26, 2023
In order to meet the combustion output requirements, a suitable nozzle needs to be installed. The nozzles used in this machine generally use fuel injection nozzles with an atomization angle of 60°. The oil pressure of the oil pump has been fully set before the whole machine leaves the factory. Without special requirements and non-professionals are not allowed to change the oil pressure of the oil pump at will to avoid damage to the oil pump. Adjustment of damper: The burner requires an appropriate amount of air to assist combustion during the combustion process, and a certain amount of air is also required to control the back pressure of the furnace. However, the amount of air will also affect combustion, so the damper of the industrial burner must be appropriately adjusted.
1. Before the Industrial Natural Gas Fired Burner is started, gently open the damper at the bottom of the burner, then turn it on. When a flame is lit, carefully observe its color, ignition power of the flame, and the speed of the radiated flame.
2. If the color of the flame is red, its ignition intensity is poor, and its flame ejection speed is slow, then continue to open the air damper until the flame is slightly yellow and slightly dazzling. Its ignition power is strong and its flame ejection speed is moderate. Can.
3. If the flame is short in length and red in color, turn down the air damper until the flame is slightly yellow and slightly dazzling, the ignition power is strong and the flame length is moderate.
4. The Natural Gas Fired Burner is installed on the stove. During combustion debugging, if there is black smoke, gradually open the damper; if there is white smoke, gradually close the damper; the damper should be small until there is no smoke.
5. When the boiler burner burns normally, turn off the power after working for a few minutes, then turn it on again after a few minutes to check whether the ignition and combustion are normal. If there is no abnormality after repeated several times, it means that the burner adjustment is completed. If the alarm light comes on after starting the burner, you need to wait at least 20 seconds before pressing the reset button again to restart.www.burners-china.com